158
Type BWC 301.A
06
08
10
13
17
Dimensions
Total length
mm
844
Total width
mm
600
Total height (programming
unit open)
mm
1155
Connections
Primary flow and return
G
1½
Heating flow and return
G
1½
Weight
kg
123
127
139
145
158
Sound power level
at
B0/W35 °C
(test with reference to DIN
EN ISO 9614-2)
dB(A)
40
41
41
41
42
Type WWC 301.A
06
08
10
13
17
Output data
to DIN EN 14511 (W10/
W35 °C, 5 K spread)
Rated heating output
kW
7.86
10.37
13.40
17.13
23.00
Cooling capacity
kW
6.70
8.84
11.44
14.56
19.54
Power consumption
kW
1.25
1.64
2.12
2.77
3.72
Coefficient of performance
ε
(COP)
6.3
6.3
6.3
6.2
6.2
Brine
(primary circuit)
Content
l
3.0
3.4
4.0
4.5
5.9
Min. flow rate (spread 4 K)
l/h
1530
2000
2570
3300
4450
Residual head (at min. flow
rate)
mbar
560
500
750
490
110
Max. flow temperature
°C
25
25
25
25
25
Min. flow temperature
°C
-5
-5
-5
-5
-5
Heating water
(secondary
circuit)
Content
l
3.0
3.5
4.0
4.6
5.7
Min. flow rate (spread 10 K) l/h
690
900
1170
1450
1990
Residual head (at min. flow
rate)
mbar
630
580
614
580
510
Max. flow temperature
°C
60
60
60
60
60
Specification
Specification
(cont.)