155
Type WW 301.A/BWS 301.A in con-
junction with "conversion kit for
water/water heat pump"
06
08
10
13
17
Electrical values, heat
pump
Rated voltage, compressor
3/N/PE 400 V/50 Hz
Rated current, compressor
A
5.5
6.0
8.0
10.3
15.0
Starting current, compres-
sor
(with starting current limiter,
not in type BW/BWS/BWC
301.A06)
A
25.0
14.0
20.0
22.0
25.0
Starting current, compressor
with stalled armature
A
26.0
35.0
48.0
51.5
75.0
Compressor fuse
A
C16A
3-pole
B16A
3-pole
B16A
3-pole
B16A
3-pole
C20A
3-pole
Protection class
I
Electrical values, control
unit
(only for type WW
301.A)
Rated voltage
1/N/PE 230 V/50 Hz
Fuse protection
B16A
Fuses
2 x 6.3 AH slow/250 V
Max. power consumption
W
1000
Power consumption in oper-
ation
W
5
Refrigerant circuit
Refrigerant
R 410 A
Fill volume
kg
1.55
1.9
2.2
2.6
3.5
Compressor
Type
Hermetic scroll
Permiss. operating pres-
sure
Primary circuit
bar
28
Secondary circuit
bar
43
Dimensions
Total length
mm
844
Total width
mm
600
Total height (programming
unit open)
mm
1155
Specification
Specification
(cont.)
5600 161 GB