95
Fault code dis-
played
System characteristics
Cause
Measures
F9
Burner in a fault state
Fan speed too low
Check fan, fan connecting cables
and fan power supply.
Press reset button
R
.
FA
Burner in a fault state
Fan idle state or set speed
not reached
Check fan, check connecting ca-
bles to fan.
Press reset button
R
.
FC
Burner in a fault state
Fan unit faulty.
Check fan unit, replace if required.
Press reset button
R
.
FD
Burner in a fault state
Burner control unit fault
Check ignition electrode, ionisation
electrode and connecting cables.
Check whether a strong interfer-
ence (EMC) field exists near the
appliance.
Press reset button
R
.
If the fault occurs sporadically, re-
place the coding card.
Replace control unit if fault is per-
manent.
FE
Burner in a fault state and ad-
ditional fault B7 is displayed.
Boiler coding card miss-
ing.
Insert the boiler coding card.
Press reset button
R
.
Replace control unit if fault per-
sists.
FE
Burner blocked or in a fault
state
Boiler coding card or main
PCB faulty, or incorrect
boiler coding card
Press reset button
R
. If the fault
persists, check the boiler coding
card and replace boiler coding card
or control unit if necessary.
FF
Burner blocked or in a fault
state
Internal fault or reset but-
ton
R
blocked.
Restart the appliance. Replace the
control unit if the appliance will not
restart.
Note
If subscriber faults occur,
"Error, subscriber ..."
is dis-
played.
Troubleshooting
Fault codes
(cont.)
5778741
Diagnosis