66
"Function, input DE3 at EA1 extension"
Setting
Explanations
None
3C:0
Operating program changeover
3C:1
External demand with set flow temperature
3C:2
Set flow temperature setting: parameter 9B
Internal circulation pump function: parameter 3F
External blocking
3C:3
Internal circulation pump function: parameter 3E
External blocking with fault message
3C:4
Internal circulation pump function: parameter 3E
External fault message
3C:5
Fault message hook-up from external devices
Brief operation, DHW circulation pump
(pushbutton function)
3C:6
DHW circulation pump runtime setting: parameter 3D
"DHW circulation pump runtime for brief operation"
Setting
Explanations
5 min
3D:5
... min
3D:0 to
3D:60
Adjustable from 1 to 60 min
"Function internal circulation pump with signal "External blocking""
Setting
Explanations
Remains in control mode
3E:0
Is switched off
3E:1
Is switched on
3E:2
"Function internal circulation pump with signal "External demand""
Setting
Explanations
Remains in control mode
3F:0
Switch off internal pump or switch on inter-
nal pump at VIUPM pump
3F:1
Is switched on
3F:2
"Function, input 96"
Setting
Explanations
Without
4B:0
Function of external hook-up at plug 96
External demand
4B:1
External blocking
4B:2
"Function of internal circulation pump for operation with low loss header or heating water buffer cylin-
der"
Setting
Explanations
Low loss header: Circulation pump always
runs on demand
51:0
Low loss header: Circulation pump only
runs on demand if the burner is running
with run-on time
51:1
Heating water buffer cylinder: Circulation
pump only runs on demand if the burner is
running with pump run-on time
51:2
Parameter level 2
General
(cont.)
5778741