74
"DHW cylinder hydraulic connection"
Setting
Explanations
Directly at boiler or upstream of low loss
header
5B:0
Downstream of low loss header
5B:1
"Function of circulation pump for cylinder heating at "External blocking" signal"
Setting
Explanations
Remains in control mode
5E:0
Is switched off
5E:1
Is switched on
5E:2
"Function of circulation pump for cylinder heating at "External demand" signal"
Setting
Explanations
Remains in control mode
5F:0
Is switched off
5F:1
Is switched on
5F:2
"Set boiler water temperature for DHW heating"
Setting
Explanations
20 K
60:20
During DHW heating, the boiler water temperature is
up to 20 K higher than the set DHW temperature
... K
60:5 to
60:25
The differential between the boiler water temperature
and the set DHW temperature is adjustable from 5 to
25 K
"Circulation pump run-on"
Setting
Explanations
2 min.
62:2
Circulation pump with 2 min run-on time after cylinder
heating
No run-on
62:0
... Min.
62:1 to
62:15
Run-on time adjustable from 1 to 15 min
"Additional function for DHW heating"
Setting
Explanations
Only if control unit has been changed to constant tem-
perature mode.
Without
63:0
Circulation pump with 2 min run-on time after cylinder
heating
1x daily
63:1
All ... Days
63:2 to
63:14
Additional function adjustable from every 2 days to ev-
ery 15 days
2x daily
63:15
"Diverter valve"
Setting
Explanations
Without
65:0
With
65:...
Information on the type of diverter valve (never adjust;
specified by the boiler coding card)
Parameter level 2
DHW
(cont.)
5778741
Parameter