70
1085.0 "Cylinder heating: Set start point"
Setting
Explanations
Start point for DHW heating
below
set DHW tempera-
ture
25
Delivered condition start point 2.5 K below set DHW
temperature
10 to 100
Adjustable start points:
10:
1.0 K ...
100: 10.0 K
Irrespective of this, the stop point is 2.5 K
above
the
set DHW temperature.
1087.0 "Max. duration, DHW heating"
Setting
Explanations
After a set period of time has elapsed, DHW heating
ends even though the set DHW temperature has not
yet been reached.
Not adjustable on gas condensing combi boilers
60
Factory setting 60 min
0
No time limit for DHW heating
1 to 240
Duration of DHW heating adjustable from 1 to 240 min
in 1 min increments
1087.1 "Min. delay until next DHW heating"
Setting
Explanations
Minimum delay before DHW heating starts again,
even though there is a demand.
Cannot be adjusted on gas condensing combi boilers
60
Delivered condition, delay of 60 min
60 to 240
Delay adjustable from 60 to 240 min in 1 min incre-
ments
1101.2 "Set speed of the primary circuit pump for DHW heating"
Setting
Explanations
Set speed of the internal circulation pump when oper-
ated as a circulation pump for cylinder heating
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %
System configuration (parameters)
DHW
(cont.)
5593201
Parameter
Summary of Contents for B2HF
Page 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Page 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Page 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Page 135: ...135 5593201 ...