96
Displayed fault
code
System characteristics
Cause
Measures
F.373
Burner in a fault state
Heat transfer too low dur-
ing calibration
Temperature limiter has
shut down.
■
Ensure adequate heat transfer.
■
Check circulation pump for faults,
scale or blockages.
■
Check 3-way diverter valve func-
tion in actuator test. Vent the sys-
tem.
■
Check function of flow sensor.
Reset the appliance.
F.377
Burner in a fault state
Post-processing ionisation
current calibration: Stabili-
sation conditions for post-
calibration not reached
Check gas type setting. If fault re-
curs, replace BCU burner control
unit (see page 109).
Reset the appliance.
F.378
Burner in a fault state
Flame loss during stabili-
sation or operating phase
■
Check gas supply (gas pressure
and gas flow switch).
■
Check flue gas recirculation.
■
Check for contamination of ioni-
sation electrode and burner
gauze assembly.
Reset the appliance.
F.379
Burner in a fault state
Flame signal not present
or insufficient
■
Check ionisation electrode con-
necting cable for damage and
ensure it is secure.
■
Check ionisation electrode, re-
place if necessary.
Reset the appliance.
F.380
Burner in a fault state
Flame is lost immediately
after flame formation (dur-
ing safety time)
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode, burner
gauze assembly:
■
Clearance to burner gauze as-
sembly
■
Contamination on electrode
Reset the appliance.
F.381
Burner in a fault state
Flame loss during operat-
ing phase
Check gas supply (gas pressure
and gas flow switch).
Check balanced flue system for
flue gas recirculation.
Check ionisation electrode, burner
gauze assembly:
■
Clearance to burner gauze as-
sembly.
■
Contamination on electrode
Reset the appliance.
F.382
Burner in a fault state
Fault counter has excee-
ded limit.
Reset the appliance. Work through
fault analysis using fault history.
F.383
Burner in a fault state
Possible contamination of
gas line
■
Check gas line for contamination.
■
Check the gas supply pressure.
■
Replace gas fan if required.
Reset the appliance.
Troubleshooting
Fault messages
(cont.)
5593201
Diagnosis
Summary of Contents for B2HF
Page 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Page 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Page 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Page 135: ...135 5593201 ...