71
Note
Parameter values in
bold
are factory settings.
424.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 1"
Setting
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
424.4 "Duration for set flow temperature increase, heating circuit 1"
Setting
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
426.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 2"
Setting
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
426.4 "Duration for set flow temperature increase, heating circuit 2"
Setting
Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min
60
Delivered condition 60 min
0 to 120
Temperature rise adjustable from 0 to 120 min
428.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 3"
Setting
Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K
0
Delivered condition increase 0 K
0 to 20
Temperature rise adjustable from 0 to 20 K
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating circuit 3, Heating circuit 4
5593201
Parameter
Summary of Contents for B2HF
Page 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Page 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Page 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Page 135: ...135 5593201 ...