522.3 "Interval until the next service"
Setting
Explanations
Interval until the next service
0
No interval selected
1
3 months
2
6 months
3
12 months
4
18 months
5
24 months
596.0 "Maximum heating output"
Setting
Explanations
A limit can be set on the maximum heating output for
heating mode.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
597.0 "Limit, max. heating output for DHW heating"
Setting
Explanations
A limit can be set on the maximum heating output for
DHW heating.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
1100.2 "Set speed of the primary circuit pump in heating mode"
Setting
Explanations
Set speed of internal circulation pump
■
In heating mode
■
With external demand
■
With demand in conjunction with a low loss header
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %
1240.0 "Operating mode of primary circuit pump"
Setting
Explanations
1
"Automatic"
Switched on regardless of current temperature level
7
Shutdown in reduced mode (in conjunction with con-
tinuous operation or when no demand via room ther-
mostat)
1411.0 "Clear maintenance messages"
Setting
Explanations
Clear maintenance messages once maintenance has
been performed.
No
0
Maintenance messages are active (if present).
Yes
1
Clear maintenance messages once.
System configuration (parameters)
Boiler
(cont.)
5593201
Parameter
Summary of Contents for B2HF
Page 33: ...33 2 2x 1 Fig 26 Installation sequence Closing the wiring chamber 5593201 Installation ...
Page 111: ...111 1 2 4 3 6 5 Fig 56 Troubleshooting Repairs cont 5593201 Diagnosis ...
Page 134: ...134 WiFi router 31 Wiring diagram 121 Keyword index Keyword index cont 5593201 ...
Page 135: ...135 5593201 ...