External unit power supply 230 V~/400 V~
■ Economy tariff and power-OFF can be
used.
■ No parameters need to be set when
using economy tariff with power-OFF.
The compressor is shut down during
the power-OFF period.
■ During power-OFF, the diagnostic
functions for the external unit are not
supported.
Note
Free terminals for internal use.
External unit power supply 230 V~
Type AWT-AC
241.A04
?
C N L
?
B
L1
N
A
241.A07
COM
Ni
?
Li
N
0
L
0
B
?
N L1
A
?
241.A10 and A13
?
N L
?
N L
C2 C1
B
?
N L1
A
A
Wiring chamber, external unit: See
page 52.
B
Power supply 230 V/50 Hz
Type AWT-AC
241.A04
241.A07
241.A10
241.A13
Recommended power
cable
3 x 2.5 mm
2
(max. 29 m)
3 x 2.5 mm
2
(max. 25 m)
3 x 2.5 mm
2
(max. 20 m)
3 x 4.0 mm
2
(max. 20 m)
or
3 x 4.0 mm
2
(max. 32 m)
3 x 6.0 mm
2
(max. 30 m)
Fuse protection
B20A
B20A
B20A
B32A
Installation sequence
Power supply
(cont.)