151
Type AWT-AC
241.B10
241.B13
Heating water
(secondary
circuit)
Contents
l
3.8
3.8
Minimum volume
l
50
50
Minimum flow rate (must be
maintained)
l/h
1600
1600
Max. external pressure drop
(RFH) at minimum flow rate
mbar
450
450
kPa
45
45
Max. flow temperature
°C
55
55
External unit electrical val-
ues
■ Rated voltage, compres-
sor
3/N/PE 400 V/50 Hz
■ Max. operating current,
compressor
A
7.85
9.89
■ Starting current, compres-
sor
A
10
10
■ Starting current, compres-
sor with stalled armature
A
16
16
■ MCB/fuse protection
A
16
16
■ IP rating
IP
24
24
Internal unit electrical val-
ues
Heat pump control unit/PCB
■ Rated voltage, control
unit/PCB
1/N/PE 230 V/50 Hz
■ Fuse protection, power
supply
1 x B16A
1 x B16A
■ Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water
heater
■ Rated voltage
1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz
■ Heating output
kW
8.8
8.8
■ Fuse protection, power
supply
3 x B16A
3 x B16A
Specification
Specification
(cont.)
5546 699 GB
Service