146
Type AWT-AC
241.A04
241.A07
241.A10
241.A13
Air intake temperature
Cooling mode
■ Min.
°C
15
15
15
15
■ Max.
°C
45
45
45
45
Heating mode
■ Min.
°C
–15
–15
–15
–15
■ Max.
°C
35
35
35
35
Heating water
(secondary
circuit)
Contents
l
2.8
2.8
3.8
3.8
Minimum volume
l
25
50
50
50
Minimum flow rate (must be
maintained)
l/h
750
1000
1600
1600
Max. external pressure drop
(RFH) at minimum flow rate
mbar
450
400
450
450
kPa
45
40
45
45
Max. flow temperature
°C
55
55
55
55
External unit electrical val-
ues
■ Rated voltage, compres-
sor
1/N/PE 230 V/50 Hz
■ Max. operating current,
compressor
A
13.5
15.7
19.6
26.5
■ Starting current, compres-
sor
A
10.5
15
10
10
■ Starting current, compres-
sor with stalled armature
A
20
25
25
32
■ MCB/fuse protection
A
16
16
20
32
■ IP rating
IP
24
24
24
24
Specification
Specification
(cont.)
5546 699 GB