41
Fitting the fan
A
B
C
D
1.
Mount fan
D
.
Note
Ensure the gasket between the fan
housing and the boiler door is cor-
rectly seated.
Replace the gasket if damaged.
2.
Plug connecting cables
a-Ö
and
a-
Ö
A into the fan.
3.
Secure Venturi mixing pipe
C
with
gas train
A
on fan
D
and plug in
connecting cables/lines if neces-
sary.
4.
Close the boiler door and tighten the
screws on the boiler door evenly and
diagonally.
Torque: 40 Nm.
5.
Secure fitting
B
to the gas supply
pipe.
Torque: 40 Nm.
Danger
Escaping gas leads to a risk of
explosion.
Check the fitting and gasket
between the fan housing and the
boiler door for gas tightness.
Making the burner electrical connections
!
Please note
Never allow cables/leads to
come into contact with hot com-
ponents.
Secure all cables/leads with
cable ties if necessary.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5794 780 GB