12
12.
Check all fittings for tightness.
Danger
Escaping gas leads to a risk
of explosion.
Check all fittings for gas
tightness.
!
Please note
The use of leak detection
spray can result in incorrect
functions.
Leak detection spray must
not come into contact with
electrical contacts.
13.
Start the burner (see page 18).
Rated heating output
kW
400
500
620
Restrictor for natural gas E
7
mm
−
21.5
−
Natural gas settings on the burner control unit
C
D
E
F
1.
Press button
S
E
for longer than 2 s.
" "
flashes.
2.
Press button
F
until display
C
shows "6" under Service.
3.
Press button
S
E
until display
C
shows "6" under Status.
4.
Press button
F
until display
C
shows "2" under Status and the cur-
rent gas type is shown under Service
(0 = natural gas or 1 = LPG).
5.
Use button
F
or
D
to select
"0" for natural gas.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5794 780 GB