52
Menu points "5" and "6" are used to
adjust configuration settings of the
burner control unit.
Note
Only make adjustments when the burner
control unit is on standby.
Configurations:
Menu
point
Description
5
Changeover from the operat-
ing display of the burner con-
trol unit phase to other process
information
6
Configuration of control func-
tion operating parameters
Menu point "5" is used to display the following process information:
Sub-menu
point
Process information
Units/scale
0
Phase
1
1
Boiler water temperature
°C
2
Flue gas temperature
°C
3
Ionisation current
I in 1/10 μA
4
Set speed
%
5
PWM manipulated variable
%
6
Actual speed
n in 10/min
7
Gas pressure switch 1
0 or 1
8
Gas pressure switch 2
0 or 1
9
Air pressure switch
0 or 1
A
Gas valve 1
0 or 1
B
Gas valve 2
0 or 1
Example: to display the ionisation cur-
rent, press the following keys:
1. S
longer than 2 s,
" "
flashes.
2.
until "5" is shown under Service.
3. S
"5" will be displayed under Sta-
tus.
4.
until "3" is shown under Service.
5. S
"3" is shown under Status and
during operation the ionisation
current is shown under Service
(e.g. 30 = 3.0 µA).
Burner control unit
Burner control unit
(cont.)
5794 780 GB