24
5.
Check the position of the rotary
damper during the start-up phase.
Rotary damper windows
B
must be
almost closed for approx. 5 s. During
this time, scale ring
D
must be at the
following settings:
Rated
heating
output
Rated
heat input
Rotary
damper
setting
P
max
(50/30 °C)
Q
max
(H
i
)
[net cv]
in kW
in kW
in °
400
381
30
620
593
20
Overview of differences between the three burner sizes
400 kW
A
A
Compensation hose
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5794 780 GB