91
Gas boiler, category II
2ELL3P
Rated boiler heating
output
P
min
-P
max
P
min
-P
max
P
min
-P
max
T
F
/T
R
= 50/30 °C
kW
80(100
*2
)-400 100(125
*2
)-500 124(155
*2
)-620
T
F
/T
R
= 80/60 °C
kW
74(93
*2
)-370
92(115
*2
)-460 115(144
*2
)-575
Rated heat input
kW
Q
min
-Q
max
(H
i
)
[net cv]
Q
min
-Q
max
(H
i
)
[net cv]
Q
min
-Q
max
(H
i
)
[net cv]
76(95
*2
)-381
95(119
*2
)-474 119(148
*2
)-593
Connection values
*3
Relative to the max. load
with
■ Natural gas E
m
3
/h
8.1-40.4
10.0-50.2
12.5-62.7
■ LPG P
kg/h
7.4-29.6
9.2-36.8
11.5-46.1
Burner type
CM2
Voltage
V
120
Frequency
Hz
60
Power consumption
W
54-540
60-700
60-900
for natural gas E and
height up to 1500 m
Modulation range
%
20-100 (25-100
*2
)
*2
Only for LPG P.
*3
The connection values are only for reference (e.g. in the gas contract application)
or to estimate the volumetric supplementary check of the settings.
Due to the factory settings, the gas pressure must not be altered from these values.
Reference: 15 °C, 1013 mbar (101.3 kPa)