Installation & User Manual
Problem
Possible cause
Solution
Water comes out of the irradiation
chamber.
Damaged or incorrectly positioned
O-ring that seals the quartz tube.
Replace O-ring.
Damaged or broken quartz tube.
Replace quartz tube.
Effect UV system is not good, not
enough reduction bound chlorine.
The UV transmission of the water
is too low.
Improve the UV transmission of
the water or select another (more
powerful) UV system.
The flow rate is too high.
Reduce the flow or select another
(more powerful) UV system.
Polluted quartz tube
Clean or replace the quartz tube.
UV lamp has too many operating
hours
Replace UV lamp and reset Timer.
UV lamp defective
Replace UV lamp and reset Timer.
Control panel defective
Replace control panel.
Incorrect sampling.
Ensure that the measuring
equipment is properly calibrated
and perform the measurement
again in accordance with the
applicable rules.
Possibly an overload of the bath.
Wait until the UV system has done
its work, reduce the number of
visitors or select a more powerful
UV system.
Effect UV system is not good, not
enough disinfection.
The UV transmission of the water
is too low.
Improve the UV transmission of
the water or select another (more
powerful) UV system.
The flow rate is too high.
Reduce the flow or select another
(more powerful) UV system.
Polluted quartz tube
Clean or replace the quartz tube.
UV lamp has too many operating
hours
Replace UV lamp and reset Timer.
UV lamp defective
Replace UV lamp and reset Timer.
Control panel defective
Replace control panel.
Incorrect sampling.
Ensure that the sampling points
are properly disinfected before
taking the water samples and
repeat the measurement.
Indicator on control box flashes
green.
Lamp almost needs to be replaced
(indicator flashes during the last
500 hours).
Make sure you have a spare lamp
on hand.
Indicator on control box lights up
red.
Lamp must be replaced
immediately, end of life is
reached.
Replace UV lamp and reset Timer.