4.4.4 UV lamps
The VGE Pro UV medium pressure UV lamps feature the unique S.B.T. (Single-end Bayonet Technology)
concept. The lamps are one-sided (Single-end) installed. If the lamp is completely inserted in the quartz
tube and the lamp socket, it can be fixed with a short rotation.
When working on the lamps, wait at least 15 minutes after switching off the UV
system before dismantling the lamps. Before dismantling the lamps and/or quartz
tubes after the lamps have been in operation, the temperature of the components
must be checked to prevent burns.
UV lamps, both low pressure (incl. Amalgam) and medium pressure, emit UV
radiation which can cause damage to skin and eyes.
See the chapter 'Lamp breakage' in the event of a lamp breakage.
4.5 Control
4.5.1 Control
The control consists of a completely closed control box with the cables connected. The control box cannot
and may not be opened. Cables may not be shortened or extended.
The control box is designed to be mounted on the wall and can easily be connected to the electricity grid
with a plug.
Before the control system is connected to the electricity grid and the lamp is
switched on, the irradiation chamber must be completely and properly installed in
the relevant pipeline network, flow through with sufficient water and be completely
connected to the control cabinet.
The UV system must be connected to a properly earthed socket with the cable fitted
to the control box and plug.
The cable length between the control and UV irradiation chamber is approximately 2
m, the cable with plug for connection to the electricity grid has a length of
approximately 1 m.
The UV lamp may only be switched on if it is 100% certain that the UV irradiation
chamber is completely filled with water and that it is continuously circulated with
sufficient water. The irradiation chamber bimetallic switch must also be mounted
correctly on the irradiation chamber.