VESDA-E VES-A00-P Product Guide
www.xtralis.com
37
4.3.6
Relays
The relays, located on the main processor card, interface to the Fire Alarm Control Panel (FACP) to
communicate faults, alarms and disabled states. The relays can be programmed using Xtralis VSC. Relays 3
and 6 are permanently set for Urgent Fault and Fire 1 respectively. Table 4-22 below illustrates the default
assignments of functions (conditions) to relays and summarizes the default behavior of each relay. Section
5.5.12 describes how to configure the relay behavior using Xtralis VSC. It is possible to assign more than one
condition to a relay.
Fire 1 Relay
If a detector relay is to be used to signal fire alarm to the Fire Alarm Control Panel (FACP) then the Fire 1 relay
must be used.
Urgent Fault and Fire 1 Relay Terminals
The Urgent Fault relay is energized during normal operation while the Fire 1 relay is only energized when a Fire
1 is detected. The operation of these two relays is summarized in the following table.
Table 4-1: Urgent Fault and Fire Relay Operation
URGENT FAULT Relay
Fire 1 Relay
No Fault
(Energized)
Fault
or unpowered state
No Fire
(De-energized)
Fire
Relay Assignments and Behaviour
l
Relays 1, 2, 4, 5, 7, 8, 9, 10, 11, 12 are fully configurable.
l
Relays 3 and 6 are fixed to Urgent Fault and Fire 1 respectively. These relays may be assigned additional
conditions.
l
Relays 3 and 6 are changeover relays. (SPDT (1 Form C)) All the other relays are single pole single throw
(SPST-NO (1 Form A)).
Relay #
Default
Assignment
Default to
Normally
Energized
Description for default configuration
Configurability
1
Disable
(Isolate) and
Standby
No
Energizes when an operator disables
(isolates) the detector. Also energizes when
the operator puts the detector into Standby
mode.
Fully
configurable
2
Minor Fault
Yes
De-energizes when a Minor Fault is
detected.
Fully
configurable
3
Urgent Fault
Yes
De-energizes when an Urgent Fault is
detected.
Note that Relay 3 is fixed Normally
Energized in order to ensure that a fault will
be signaled when power to the VES-A00-P
is removed. See Table 4-1.
Urgent Fault
cannot be
removed. Other
conditions can
be added.
Fixed Normally
Energized
4
Alert
No
Energizes when the Alert alarm is initiated.
Fully
configurable
Table 4-2: Default Relay Assignments
Summary of Contents for VESDA-E VES-A00-P
Page 2: ......
Page 10: ...VESDA E VES A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VES A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 50: ...VESDA E VES A00 P Product Guide 44 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VES A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 84: ...VESDA E VES A00 P Product Guide 78 www xtralis com This page is intentionally left blank ...
Page 101: ...VESDA E VES A00 P Product Guide www xtralis com 95 Figure 7 21 Undo Sampling Module screws ...
Page 106: ...VESDA E VES A00 P Product Guide 100 www xtralis com ...
Page 108: ...VESDA E VES A00 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VES A00 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VES A00 P Product Guide 106 www xtralis com This page is intentionally left blank ...
Page 118: ...VESDA E VES A00 P Product Guide 112 www xtralis com This page is intentionally left blank ...
Page 124: ...VESDA E VES A00 P Product Guide 118 www xtralis com Z zone 55 56 79 113 ...