Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 41
Distribution Devices
See
Distribution Devices and Load Lug Locations - Power/Distribution Bays
Distribution Device and Load Lug Locations
at the beginning of this section for illustrations of distribution device and load lug mounting
locations.
218 Circuit Breaker Assemblies
Features
♦
Each circuit breaker assembly is equipped with a shunt for load current measurements.
♦
Bolts into bay's distribution device mounting positions.
♦
Load lug adapter plate provides 3/8" clearance holes on 1" centers for installation of customer provided two-hole lugs.
For load return lug requirements, refer to
Power/Distribution and Power Only Bays External Busbars
the distribution only bays, the load return leads are terminated outside the bay to customer provided return busbars.
Restrictions
Load should not exceed 80% of device rating.
Refer to
for required distribution bus mounting positions.
Each distribution bus is divided into half. Each half MUST be populated with distribution devices as shown in the illustrations
at the beginning of this section, without skipping any distribution device mounting positions within each half.
Four (4) position devices can only be installed in the 1st four or last four positions within each half of a distribution bus. This
is because the lug adapter plate for four (4) position devices can only be installed in positions starting with the load busbar
tops even with each other (not staggered).
Divide distribution equally between rows.
Refer to the illustrations in this section for lug and wire size restrictions.
Load return leads are terminated outside the distribution only bay to customer provided return busbars.
Ordering Notes
1)
Order circuit breaker assemblies and load lug adapter kits per
. Load lug adapter kits also contain the necessary
hardware to mount the circuit breakers. For 1-pole circuit breakers in a List 16/List 116, List 17/List 117, List 18/List 118,
List 22/List 122 Distribution Only Bay, also order circuit breaker hardware kit P/N 558709. This hardware is used to
mount the circuit breaker.
2)
See