Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 4
General Specifications
See detailed specifications on page 106.
Family:
Vertiv™ NetSure™
Spec. No.:
582140000
Model:
8200
NLDB
(208V Input Power/Distribution and Power Only Bays) (NCU Controller)
8200
NLEB
(480V Input Power/Distribution and Power Only Bays) (NCU Controller)
8200
NL
-
B
(Distribution Only Bay) (NCU Controller)
802
NLDB
(208V Input Power/Distribution and Power Only Bays) (MCA Assembly)
802
NLEB
(480V Input Power/Distribution and Power Only Bays) (MCA Assembly)
802
NL
-
B
(Distribution Only Bay) (MCA Assembly)
Input Voltage
R48-12000e: Nominal 480 volts AC, three phase, 60 Hz, with an operating range of
340 to 528 volts. Acceptable input frequency range is 57 to 63 Hz.
or
R48-12000Le: Nominal 208 volts AC, three phase, 60 Hz, with an operating range
of 176 to 264 volts. Acceptable input frequency range is 47 to 63 Hz.
Output Voltage:
-48 Volts DC
Output Capacity:
System:
16,000 Amperes, maximum
Power Only Bay:
2200 Amperes, maximum
Power/Distribution Bay:
2400 Amperes, maximum
Distribution Bus
(two Distribution Buses
per Power/Distribution Bay):
1200 Amperes
Rectifier:
200 A / -48 V
Distribution Only Bay:
6000 Amperes, maximum
Distribution Bus:
(four Distribution Buses
per Distribution Only Bay)
1500 Amperes, maximum
Optional Distribution Panel:
(Bullet Nose Circuit
Breakers and/or TLS/TPS
Fuses) (one optional
Distribution Panel per
Distribution Only Bay)
500 Amperes, maximum
Agency Approval:
Power/Distribution Bay and Distribution Only Bay: Listed UL 1801, NEBS
Power Only Bay: UL 60950, NEBS
Framework Type:
Seismic Rated (Zone 4) Box Framework
Power/Distribution Bay:
Width:
24”, plus 10” if PDSC used
Depth:
30”
Height:
93.5” Lists 1 and 11, 84” Lists 2 and 12
Access:
Single Bay Plants:
Front Access for Installation, Maintenance, and Operation.
Multi-Bay Plants:
Front and Rear Access for Installation and Maintenance, Front for Operation.