Distribution Only Bay DC Input Cable Sizes and Lugs Selection
Features
♦
3/8” clearance holes on 1" centers are provided for installation of customer provided DC input cables terminated in two-
hole lugs. These are accessed from the rear of each Distribution Bay.
♦
For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting hardware
.
Maximum size of wire to be connected to a single lug position is 750 kcmil (2 per lug position).
Maximum lug width, 2.000 inches.
Ordering Notes
1)
DC input cable size varies depending on power requirements, therefore no specific information is provided for cable size.
Refer to Table 14 for recommended cable sizes and lugs at rated maximum bay load (6000 amperes). When making
connections, observe correct polarity.
2)
Lugs should be crimped per lug manufacturer’s specifications.
Ambient Operating
Temperature
(1)
Loop
Length
(2)
(Ft)
Recm 90
°
C
Wire Size
(1, 2)
Recommended Crimp
Lug
(3)
30°C
112
(10) 750 kcmil
245392000
40°C
112
(10) 750 kcmil
157
(14) 750 kcmil
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for
copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at rated full load output
current of the bay for the loop lengths shown. Loop length is the sum of the lengths of the positive and
negative leads.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Lugs should be crimped per lug manufacturer’s
specifications.
Table 14
Recommended Distribution Bay DC Input Cable Size and Lug Selection