Optional Load Return Lug Extension Busbar Assembly
Features
♦
Provides a load return lug extension busbar which mounts to an external top-mount ground (load return) busbar
assembly.
♦
Provides for installation of customer provided two-hole lugs with 3/8" clearance holes on 1" centers.
Restrictions
Rated for 1000 amperes.
Requires an external top-mount ground (load return) busbar assembly; P/N 514688, 514689, 514690, or 514691.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Ordering Notes
1)
Order a load return lug extension busbar assembly per bay as required, P/N 514543.
External Top-Mount Ground (Load Return) Busbar Assemblies
(for use with External Top-Mount Battery Input Busbar Assembly P/N 554873)
P/N 514688 (6000A) (for use with List 1 and 11, no PCU AC Input
Service Cabinet, or List 3, 4, 5, 13, 14, or 15)
P/N 514689 (10000A) (for use with List 1 and 11, no PCU AC Input
Service Cabinet, or List 3, 4, 5, 13, 14, or 15)
P/N 514690 (6000A) (for use with List 2 and 12
e/w List 30 or 31 PCU AC Input Service Cabinet)
P/N 514691 (10000A) (for use with List 2 and 12
e/w List 30 or 31 PCU AC Input Service Cabinet)
P/N 514689 Shown
P/Ns 514688, 514690, and 514691 Similar
P/N 514689
Mounted to
P/N 554873
GROUND (LOAD RETURN)
(see Detail B for hole size
and spacing dimensions)
GROUND (LOAD RETURN)
(see Detail B for hole size
and spacing dimensions)
(see Detail C for illustration
of assembly mounted on top
of Power/Distribution Bay)
View #1
View #2
View #3
View #4