LIST DESCRIPTIONS
List Numbers
List A: 480 VAC Plant Input Voltage
Features
♦
Specifies 480 VAC plant input voltage.
List B: 208 VAC Plant Input Voltage
Features
♦
Specifies 208 VAC plant input voltage.
List 1 and 101: Primary Power/Distribution Bay (Common Equipment)
Features
♦
Provides common equipment for one (1) “power and distribution” bay rated for up to 2400 amperes.
♦
Mounted in a 93.5"H x 24"W x 30"D box framework.
♦
Provides ten (10) rectifier mounting positions.
♦
Provides an AC input termination panel that accepts ten (10) AC input branch circuits, one (1) per rectifier mounting
position.
♦
Provides forty-eight (48) distribution device mounting positions.
♦
Provides two (2) buses of distribution. When used with the MCA, each bus contains a monitoring circuit card; which can
be set for no group designation, Group A designation, or Group B designation.
♦
Configured for a 4000 A internal bus or external main battery termination bars.
♦
List 1: Equipped with an MCA Assembly and provides mounting for optional LMS Main CPU circuit card. Provides a
seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit cards, and/or optional LMS
I/O circuit cards. Two (2) MCA customer alarm relay circuit cards provided.
♦
List 101: Equipped with an NCU controller and front panel touch screen PC for local access to the NCU webpages.
Includes an IB4 board which provides a Network connection point for NCU remote access. Includes the IB2 NCU
interface board (provides eight (8) programmable form C- relay outputs, eight (8) programmable binary inputs, and two
(2) temperature inputs). Includes the EIB NCU extended interface board (provides five (5) programmable form-C relay
outputs, two (2) temperature inputs, three (3) shunt inputs, and eight (8) battery midpoint inputs).
♦
Expandable either left or right.
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Ordering Notes
1)
(208 VAC Input).
2)
Order rectifiers as required per
(480 VAC Input) or
(208 VAC Input).
3)
Order distribution fuse and/or circuit breaker devices as required per
in the
ACCESSORY
DESCRIPTIONS
section.
4)
List 1: Order additional MCA customer alarm relay circuit card(s) as required per
cards per
. Order optional LMS Monitor and LMS options as required per
Battery Charge Temperature Compensation Probe as required per
Battery Charge Temperature Compensation Probe for
ACCESSORY DESCRIPTIONS
section.
5)
List 101: Order temperature probes as required per
in the
ACCESSORY DESCRIPTIONS
section.
6)
Order bay grounding lugs as required per
Power/Distribution Bay Frame Grounding Wire Sizes and Lugs
in the
ACCESSORY DESCRIPTIONS
section.
7)
Order load distribution lugs as required per
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire
in the
ACCESSORY DESCRIPTIONS
section.
8)
Order battery cable lugs as required per
Power/Distribution Bay Battery Cable Sizes and Lugs
in the
ACCESSORY
DESCRIPTIONS
section.