Distribution Devices and Load Lug Locations - Power/Distribution Bays
Each power/distribution bay has two (2) distribution buses. Each distribution bus has twenty-four (24) fuse/circuit breaker
device mounting positions. Note that the various fuse/circuit breaker devices require different number of mounting positions,
as detailed in the following sections. Note also that each distribution bus is divided into half, and each half MUST be
populated with distribution devices from left-to-right, without skipping any distribution device mounting positions within each
half. The load side of each fuse/circuit breaker mounting position is bused up to the top of the bay. Each fuse/circuit breaker
device requires a load lug adapter plate that mounts to the appropriate load side busbars at the top of the bay (except bullet
nose-type devices which use the existing busbars provided at the top of the bay and do not require a lug adapter plate). Load
return leads are terminated either inside the bay if equipped with the optional internal ground busbar, or outside the bay if
equipped with the optional external ground busbar mounted on top of the bay (see
Optional Power/Distribution Bay Internal
Power/Distribution and Power Only Bays External Busbars
Bus #1
Distribution Device
Mounting Location
Bus #2
Distribution Device
Mounting Location
Load Lug and/or
Load Lug Adapter Plate
Mounting Location
Load Lug and/or Load Lug Adapter Plate
Mounting Location Dimensions
0.625"
0.765"
1/4-20 Studs
and Hardware
Left Half
Distr. Bus
#1 and #2
Right Half
Distr. Bus
#1 and #2
Note: Each half of each bus MUST be populated
with distribution devices from left-to-right,
without skipping any distribution device mounting
positions within each half.
Notes:
1. Maximum size of wire to be connected
to a single lug position (without using an
adapter plate) is 2 AWG.
2. Maximum lug width (without using an adapter
plate) is 0.671 inches.