Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 50
Ampere
Rating
Number of Poles
(and mounting positions required
in Bullet Nose-Type Circuit
Breaker/Fuseholder Mounting
Assembly)
Part Number
Electrical Trip
1
(White Handle)
Electrical/
Mechanical Trip
2
(Black Handle)
1
1
142856
142878
3
1
142857
142879
5
1
142858
142880
10
1
142859
142881
15
1
142861
142882
20
1
142862
142883
25
1
142863
142884
30
1
142864
142885
35
1
142865
142886
40
1
142866
142887
45
1
142867
142888
50
1
142868
142889
60
1
142869
142890
70
1
142870
142891
75
1
142871
142892
80
1
142872
142901
100
1
142873
142902
125
2
142874
142903
150 (see
Caution
below)
2
142875
142904
200 (see
Caution
below)
2
142876
142905
Order a Bullet Nose-Type Circuit Breaker/Fuseholder Mounting Assembly, P/N 513747, for every six circuit
breaker/fuseholder combinations ordered. Each bullet nose-type circuit breaker/fuseholder mounting assembly requires six
(6) distribution bus mounting positions.
See
for recommended load distribution wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device within the circuit breaker/fuseholder mounting
assembly.
Table 4
Rocker-Handle Bullet Nose-Type Circuit Breakers and Bullet Nose-Type
Circuit Breaker/Fuseholder Mounting Assembly