Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
78
7.
Verify and set the SCU+ controller as required for your application. Refer to the separate SCU+ User
Manual for procedures.
NOTE!
Any LVD is on LVD1.
Verifying the Configuration File
Your SCU+ was programmed with a configuration file that sets all adjustable parameters. The version number
of the configuration file can be found on the Configuration Drawing (C-drawing) that is supplied with your
Power System documentation, and on a label located on the SCU+. You can verify that the correct
configuration file has been loaded into your SCU+ by performing the following procedure.
Procedure
1.
With the Main screen displayed, press ESC. A screen displays the software version and configuration
version number.
2.
Press ESC to return to the Main screen.
Checking System Status
Procedure
1.
Observe the status of the indicators located on the Rectifier Modules and SCU+. If the system is
operating normally, the status of these is as shown in
Table 7:
Status and Alarm Indicators
Component
Indicator
Normal State
Rectifier
Modules
Power
(Green)
On
Protection
(Yellow)
Off
Alarm
(Red)
Off
SCU+
Status
(Green)
On
Observation
(Yellow)
Off
Major or Minor
Alarm (Red)
Off
Configuring the SCU+ Identification of Rectifier Modules
When Rectifier Modules are all installed prior to applying power to the system, the order in which the SCU+
identifies the Rectifier Modules is by serial number (lowest serial number is Rect 1, next lowest is Rect 2, etc.).
If you prefer the SCU+ to identify the Rectifier Modules by position in the shelf (for example, 1-3 from left to
right), perform the following procedure.