Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
32
adhesive surface, and affix the probe to a clean, dry surface. Note that temperature probes with a mounting tab
are also available (see SAG582136700).
Table 1:
Programmable Digital Inputs (Factory Default)
Programmable
Digital Input
IB2 Pin No.
Digital Input Cable Color
Scheme
Dedicated to...
1
J3-2
+
Internal Wiring
Internal Load
Circuit Breaker /
Fuse Alarm
J3-1
–
Internal Wiring
2
J3-4
+
Jumpered to J3-2
(Battery Return)
External Battery
Circuit Breaker Alarm
J3-3
–
O-R
3
J3-6
+
R-BL
User Defined
J3-5
–
BL-R
4
J4-2
+
W-S
User Defined
J4-1
–
S-W
5
J4-4
+
W-BR
User Defined
J4-3
–
BR-W
6
J4-6
+
W-G
User Defined
J4-5
–
G-W
7
J5-2
+
W-O
User Defined
J5-1
–
O-W
8
J5-4
+
W-BL
Emergency Stop
(User Pre-Defined)
J5-3
–
BL-W
--
J5-5
Not Used
Not Used
--
J5-6
ALERT!
All conductors in the Alarm Cable may be connected within the cabinet. Shorting or grounding
of unused conductors may result in service interruption or equipment damage. Therefore insulate all
conductor ends not being used in your application.