Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
52
Figure 22:
External Interface Connections (cont’d from previous page)
Yellow Jumper/Alarm
Lead (P/O Cabinet)
Orange wire on
541434 not used
Procedure
1. Remove quick connect terminal from YELLOW battery
cabinet alarm lead and wire per table below.
1st BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Cabinets
alarm
wire
2nd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
3rd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Connect to
shelf per
table below.
alarm
wire
alarm
wire
541311 Alarm Cable
on shelf
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Pin 3 of J3 on Customer Interface board
(negative side of Digital Input 2)
O-R Lead of 541311
Splice and heat shrink tubing included with 541311