NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
56
Procedure
NOTE!
The initialization routine takes several minutes. During that time various alarm indicators may
illuminate on the NCU front panel and an audible alarm may sound. Disregard all alarms. An audible
alarm can be silenced at any time by momentarily depr
essing the ENT k
ey on the NCU Controller.
1.
After the NCU is powered on, the display shows the logo screen. The controller is initializing.
2.
When initialization is complete, the language screen appears. Press the up or down arrow key to select
the desired language. Press the ENT key to confirm the selection.
3.
The Main Menu displays.
4.
System information is displayed in multiple screens. Press the ESC key to view other system
information. Press the down arrow key to view the next screen. Press the ESC key to return to the Main
Menu.
5.
From the Main Menu, press the UP and DOWN keys to highlight the desired Menu graphic in the Main
Menu. Press the ENT key to enter the selected menu.
Press the UP and DOWN keys to highlight
the desired Menu graphic in the Main Menu.
Press the ENT key to enter the selected menu.
Date and time are
alternately displayed.
Green - No Alarm
Red - Alarm
Sys Cap Used: 22.3 %
100%
53.5 V
3600.0 A
09:22:58
Main Menu
Graphics
Menu Name
Description
Alarm
(Green - No Alarm)
(Red - Alarm)
View active alarms and
alarm history.
Settings
Gain access to the NCU
Controller’s settings menus.
Input Power
View AC, Solar, DG, and
Wind related information.
Module
View rectifier /converter
related information.
DC
View DC equipments
related information.
Battery
View battery related
information.