Unit Remote Sensors Mode
When controlling at the unit level, selects the method of using the inlet-rack temperature readings from the control
sensors to control fan speed. Options are:
•
Maximum: Use the highest temperature reading of the sensors set to Control.
•
Average: Use the average of the readings from the sensors set to Control and included in AVG.
Unit Remote Sensors included in AVG
When Unit Remote Sensors Mode is
Average
, selects the number of sensors used to calculate the average
temperature.
•
If the number selected is smaller than the number of REM Sensors set to Control, only the highest readings are
used for the calculation.
NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
9.4.2 Wired Remote Sensor—Sensor Property Options
Function
Sets the function of the sensor when Unit Remote Sensors Mode is enabled.
•
Disable: Sensor readings are ignored.
•
Reference: Sensor readings are considered for Max Rack Temp, but are not used in maximum/average
calculations.
•
Control: Sensor readings are used in maximum/average calculations.
Left Lead Current Value
Current reading of the left sensor probe. The left probe is always a temperature reading.
Left Lead Offset
Correction (calibration) value added to the reading. Used in the event that the sensor reading is incorrect.
•
May be a positive or negative value.
Name
Custom, descriptive name to assist in identifying the sensor’s location/function in the facility, for example, the name of
the rack on which it is installed. The name is limited to:
•
Up to four alphanumeric characters in length
•
Upper or lower case characters
•
The following special characters: & * / . + - : @ \.
9 Configuring Auxiliary Devices
87
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...