NOTE: Sensors are connected in a daisy chain via CANbus cabling to the cooling-unit control board. You can extend
the sensor network (up to 10) by adding sensors to the end of the chain and adjusting the termination settings. Do not
run individual wires from the sensors to the cooling unit.
1.
Apply numbered stickers to the sensor housing that corresponds to the sensor’s position in the chain.
2.
Locate the DIP-switch hole on the rear of the sensor housing, Figure 12.5 below.
– or –
If the hole is not present, or the settings are difficult to make through the hole, remove the cover by removing
the Phillips-head screws (typically 3). See Figure 12.5 below.
NOTE: Use the non-conductive DIP-switch tool (included) or a similar tool to set switches. Do not insert any metal
object into the sensor case.
Figure 12.5 DIP Switch Opening/DIP Switches Inside of 2T Sensor
Item
Description
1
Hole in sensor housing
2
Cover removed
13 Hardware Installation
111
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...