Event
Description
PB1
COMMUNICATE
FAIL
Ethernet communications failure. Pump not shut down.
•
Event is reset when condition clears.
USB communications failure. Pump not shut down.
•
Event is reset when condition clears.
PB2
COMMUNICATE
FAIL
Ethernet communications failure. Pump not shut down.
•
Event is reset when condition clears.
USB communications failure. Pump not shut down.
•
Event is reset when condition clears.
PB1 COND TO
PUMP TEMP
Temperature variance from condenser 1 output to pump 1 input exceeds allowed parameters. Pump shut down.
•
Event is reset when iCOM requests a new startup.
PB2 COND TO
PUMP TEMP
Temperature variance from condenser 2 output to pump 2 input exceeds allowed parameters. Pump shut down.
•
Event is reset when iCOM requests a new startup.
MM Cycle Lock
Out
Liebert® EconoPhase operating in Mixed Mode has failed to control cooling 10 times in 6 hours.
•
Mixed Mode operation is disabled until the event is manually reset.
PB Cycle Lock
Out
Liebert® EconoPhase in Pump Mode has failed to control cooling 5 times consecutively at full-pump-capacity temperature conditions.
•
EconoPhase operation is disabled until the event is manually reset.
Table 4.4 Events Specific to Liebert EconoPhase (continued)
4.4 Enabling the Audible Alarm Notification
1.
Touch
, then
>
Display Options
>
Display Properties
.
The UNIT DISPLAY panel opens.
2.
Touch the
Alarm Buzzer Pattern
value, and select a pattern from the drop-down list.
•
Selecting
None
disables the audible notification.
3.
Touch
Save
to save the property settings.
•
Touch
Cancel
to discard changes.
4.5 Remote Alarm Device and Customer Input Events
Remote alarm devices are various sensors and detectors outside the cooling unit that provide information about conditions
and situations that may affect operation. Remote alarm devices (RAD) include smoke detectors, filter condition, valve status.
Included in the RADs option are up to four customer input events depending on cooling unit configuration. In some cases,
two additional, optional customer input events are available. See
Setting Up Customer Input Events
RAD and customer input notifications are set in the same way as other events. See
Setting Alarm/Warning Notification
Vertiv™ | Liebert® iCOM™ Installer/User Guide
52
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...