Cooling unit
Inputs available
Liebert® DS Water/Glycol Cooling
0
Models without high pressure transducers may have 2.
Liebert® PDX™ Air-Cooled
3
1 is used for low pressure transducers.
Liebert® PDX Water/Glycol Cooled
2
1 is used for a low pressure transducer. Optionally, a second for a high pressure
transducer.
Table 12.5 Number of Analog Inputs Available by Cooling Unit Type (continued)
13.5 Installing the Unit to Unit Network
13.5.1 Required Network Equipment
Ethernet cable CAT5 or greater
•
Maximum cable length is 328 ft (100 m).
•
An Ethernet repeater is required for cable lengths greater than 328 ft (100 m).
Network switch
•
IEEE 802.3; IEEE 802.3u
•
10/100 Mbps speed
•
Multiple 10/100 RJ-45 ports, one shared.
•
RJ-45 up link port
NOTE: Up to 32 cooling units may be connected in a unit to unit (U2U) network.
13.5.2 Planning Wiring Runs
When planning the layout of the conditioned space, consider the following:
•
Good wiring practices.
•
An Ethernet repeater is required for cable lengths greater than 328 ft (100 m).
•
A private network that only connects and manages the cooling units is required.
•
Keep control and communication cables away from power cables to prevent electromagnetic interference.
•
Keep cables away from noise introducing device such as machines, fluorescent lights and electronics.
•
Do not bend cables to less than four times the diameter of the diameter of the cable.
•
Do not deform cables when hanging or securing in bundles.
•
Do not exceed 25 lb (11 kg) of tension when pulling cables to avoid stretching.
•
Do not damage cables when securing them. Use only approve hangers, such as telephone wire/RG-6 coaxial-
wire hangers.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
126
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...