Low Pressure Status
Status of compressor’s low pressure switch.
Status HT1
Count of times compressor is powered off for high scroll temperature.
11.4.2 Resetting High Pressure Alarm Code
When a high pressure problem has caused a compressor to lock off, resetting the High Pressure Alarm Code to zero unlocks
the compressor for operation.
NOTE: Cycling main power of the cooling unit will also unlock the compressor.
1.
Touch
, then
>
Diagnostic/Service
>
Diagnostics
>
Compressor Circuit N
in the Category list (where
N is the circuit number).
2.
On the COMPRESSOR CIRCUIT panel, touch
Set to Zero
next to High Pressure Alarm Code, then touch
Save
.
The code is reset and the compressor can now operate.
11.4.3 Resetting Low Pressure Alarm Code
When a low pressure problem has caused a compressor to lock off, resetting the Low Pressure Alarm Code to zero unlocks
the compressor for operation.
NOTE: Cycling main power of the cooling unit will also unlock the compressor.
1.
On the Service menu, touch
Diagnostic/Service
>
Diagnostics
.
The DIAGNOSTICS panel opens.
2.
Touch
Compressor Circuit N
in the Category list
(where “N” is the circuit number)
.
3.
On the COMPRESSOR CIRCUIT panel, touch
Set to Zero
next to Low Pressure Alarm Code, then touch
Save
.
The code is reset and the compressor can now operate.
11.4.4 Resetting High-temperature Alarm Counter
1.
Touch
, then
>
Diagnostic/Service
>
Diagnostics
>
Compressor Circuit N
in the Category list
(where
“N” is the circuit number)
.
2.
On the COMPRESSOR CIRCUIT panel, touch
Set to Zero
next to High Temperature Alarm Counter, then touch
Save
. The code is reset and the compressor can now operate.
11.5 Diagnosing Electronic Expansion Valve Issues
1.
Touch
, then
>
Diagnostic/Service
>
Diagnostics
>
Electronic Expansion Valve N
in the Category
list.
The ELECTRONIC EXPANSION VALVE panel displays.
2.
Refer to
Diagnostics—Electronic Expansion Valve Options
on the facing page for descriptions of diagnostic
options.
Vertiv™ | Liebert® iCOM™ Installer/User Guide
98
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...