NOTE: Depending on the type of thermal management unit, included components, and control settings of your
system, all of the options listed may not be available on your iCOM display.
2.
Before you touch a specific analog input, the properties panel lists the inputs along with their configuration
status:
•
Factory Std
indicates that the input is configured for a factory installed component such as a pressure
transducer.
•
Not Config
indicates that the input is configurable.
3.
Locate the DIP switches on the control board and program the input type according to Table 9.1 below.
Figure 9.1 below shows the switch and on/off setting.
Analog Input Number
Input #1
Input #2
Input #3
Input #4
Not Used
Control Board Switch Number
1
2
3
4
5
6
7
8
9
10
Analog Input device value
0 – 10 VDC
Off
Off
Off
Off
Off
Off
Off
Off
—
—
0 – 5 VDC
On
Off
On
Off
On
Off
On
Off
—
—
4 – 20 mA
On
On
On
On
On
On
On
On
—
—
Table 9.1 DIP Switch Settings for Analog Input Connection
NOTE: Up is on, down is off on the DIP switch. Switches 9 and 10 are not used.
Figure 9.1 Analog Connection DIP Switches on the Control Board
4. On iCOM, touch
, then
>
Auxiliary Device Setup
>
Analog Input
> Customer Analog Inputs, the
touch an Analog Input. The ANALOG INPUT PROPERTIES for that device displays.
5.
Select the configuration and touch
Save
.The analog input is configured.
NOTE: The Airflow, Static Pressure and Fluid Flow analog-input settings configure factory options and require special
instruction. Contact Vertiv™ Technical Support at 1-800-543-2778.
9 Configuring Auxiliary Devices
85
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...