13.5.4 Wiring Cooling Units without Wall Mount Displays
NOTE: Cooling units are factory wired for stand-alone operation. Do not connect the U2U network cabling before
setting the U2U network configuration/groups. Network communication conflicts and unreliable display readings will
result.
NOTE: Before you begin, refer to
Preparing for U2U Group Set Up
on page 57, and
Configuring U2U Network Settings
To connect two cooling units with a touchscreen, a network switch is not needed:
•
Connect a crossover CAT5 cable to the ETH-2 connector on the rear of each display as shown in Figure 12.19
below.
Figure 12.19 Connection between Only Two Cooling Units—No Network Switch Needed
Item
Description
1
Touchscreen (rear view)
2
Ethernet cable (field-supplied)
3
Ethernet cable (factory-supplied)
4
iCOM I/O board
Vertiv™ | Liebert® iCOM™ Installer/User Guide
128