EXS
User Manual 10H52267UM60 - Rev. 1 - 09/2018
71
Silkscree
n
Port name
Pin No.
Pin name
Meaning
Remarks
Cleared.
Pin5 and Pin7 are shorted to enable this
function
J13
1
9
EXT_MBB
On Generator / Transfer to Inverter
Inhibited / External MIB / External MBB
(default) / Module Output Breaker /
Battery Ground Fault / Charger Shut-down
/ ECO Inhibited (Inverter Mode Preferred)/
Start Battery Maintenance Self-check /
Stop Battery Maintenance Self-check
/Alarm Cleared.
Pin9 and Pin11 are shorted to enable this
function
Configurable input
dry contact J13-9
11
GND_SELV
J13
1
13
GEN_MODE
On Generator (default) / Transfer to
Inverter Inhibited / External MIB / External
MBB / Module Output Breaker / Battery
Ground Fault / Charger Shut-down / ECO
Inhibited (Inverter Mode Preferred) / Start
Battery Maintenance Self-check/ Stop
Battery Maintenance Self-check /Alarm
Cleared.
Pin13 and Pin15 are shorted to enable this
function
Configurable input
dry contact J13-13
15
GND_SELV
2
Inhibit_trans_to
_inverter
On Generator / Transfer to Inverter
Inhibited (default) / External MIB /
External MBB / Module Output Breaker /
Battery Ground Fault / Charger Shut-down
/ ECO Inhibited (Inverter Mode Preferred)
/ Start Battery Maintenance Self-check/
Stop Battery Maintenance Self-check
/Alarm Cleared.
Pin2 and Pin4 are shorted to enable this
function
Configurable input
dry contact J13-2
4
GND_SELV
6, 8, 10
Default
12
TEM_DETECT_
CONTROL
Built-in battery temperature detection
control
14
TEMP_PULSE_
IN
Built-in battery temperature detection
input
16
GND_SELV
GND
J14
2
Output dry
contact and
REPO port
1
On_Battery_A
System Alarm /On Battery (default)
/Battery Low Capacity /UPS Fault / On
Bypass / UPS /Remote EPO / Main input
abnormal / On Maintenance Bypass / Load
Shed Signal 1 / Load Shed Signal 2 /
Internal MBB Closed.
Pin1 and Pin3 shorted for alarm state.
Note: We recommend adopting the switch
with normally-closed auxiliary contact
when load shed signal is selected.
Configurable input
dry contact J14-1/3
3
On_Battery_B
5
Summary_Alar
m_A
System Alarm (default) /On Battery
/Battery Low Capacity /UPS Fault / On
Bypass / UPS /Remote EPO / Main input
abnormal / On Maintenance Bypass / Load
Shed Signal 1 / Load Shed Signal 2 /
Configurable input
dry contact J14-5/7
J14
2
7
Summary_Alar
m_B