Component
Type
Text Display
ID
Description
MUN
Status
MUN/DSP are not
Sync with SYNW
08-097
—
MUN
Status
Life Measures
Sampling Started
08-098
Ignore measures history and restart sampling from current time.
MUN
Status
System Time
Moved Ahead
08-110
Set when device time is moved ahead after time adjustment from Life Station.
MUN
Status
System Time
Moved Back
08-111
Set when device time is moved back after time adjustment from Life Station.
MUN
Alarm
CAN
Communication
Loss
28-008
Set when CAN telegram are not received for 10 seconds.
Reset when a general stage telegram is received.
MUN
Alarm
UPS Model cannot
be identified
28-056
UPS model not detected.
Rectifier
Status
Rectifier is off
02-000
—
Rectifier
Status
Rectifier is turning
on
02-001
—
Rectifier
Status
Rectifier is on
02-002
—
Rectifier
Status
Rectifier fault
02-004
Set as either
blocking
or
non-blocking
.
Rectifier
Status
Rectifier Warning
02-009
Set when at least one warning is active.
Rectifier
Status
No pre-charge in
progress
02-010
No pre-charge active. Active while mains is out of limits.
Rectifier
Status
pre-charge in
progress
02-011
Hold off delay and resistor pre-charge.
Rectifier
Status
Walk-in in progress
02-012
Rectifier current limit ramp.
Rectifier
Status
pre-charge finished
02-013
Pre-charge finished. Active while mains is OK.
Rectifier
Status
Rectifier Power
Limitation Active
02-048
Set when the input current is limited by standard or customer limit. (See Overload
specification.)
Rectifier
Status
Rectifier Current
Limit
02-049
Set when input current reaches the limit defined by P 1740.11 and lasts more than 3
ms but less than 10 ms.
Rectifier
Status
Rectifier Non-
Blocking Fault
02-050
Set when a non-blocking fault in rectifier stage is set.
Rectifier
Status
Rectifier fault
02-070
Set when a customer blocking fault flag is present (not yet defined).
Rectifier
Status
Rectifier Warning
02-071
Set when at least one customer warning is active (not yet defined).
Rectifier
Status
Rectifier Non-
Blocking Fault
02-072
Set when a customer non-blocking fault in stage is set. (not yet defined).
Rectifier
Status
Rectifier Stopped -
Fault
02-092
—
Rectifier
Status
Rectifier Inhibited
02-093
Set when the rectifier pulse is inhibited due to DC overvoltage.
Table A.2 Alarm Messages (continued)
Appendices
61
Summary of Contents for Liebert EXL S1
Page 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...
Page 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...
Page 52: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 48 This page intentionally left blank...
Page 74: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 70 This page intentionally left blank...
Page 130: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide...