Component
Type
Text Display
ID
Description
Inverter
Fault
Overtemperature
36-127
Inverter B overtemperature fault Phase W-C
Inverter
Fault
Inverter DC/AC de-
saturation
36-128
De-saturation Phase U group B
Inverter
Fault
Inverter DC/AC de-
saturation
36-129
De-saturation Phase V group B
Inverter
Fault
Inverter DC/AC de-
saturation
36-130
De-saturation Phase W group B
Inverter
Fault
Temp Probe B
Broken Phase U-A
36-131
Inverter temperature sensor fault SW detected; based on M.I. value outside sensor
limit interval -15°C < T< +150°C for 60 seconds (P 780.23).
Inverter
Fault
Temp Probe B
Broken Phase V-B
36-132
Inverter temperature sensor fault SW detected; based on M.I. value outside sensor
limit interval -15°C < T< +150°C for 60 seconds (P 780.23).
Inverter
Fault
Temp Probe B
Broken Phase W-C
36-133
Inverter temperature sensor fault SW detected; based on M.I. value outside sensor
limit interval -15°C < T< +150°C for 60 seconds (P 780.23).
Inverter
Fault
Overtemperature
Choke B Ph. U-A
36-134
Inverter filter overtemperature. Any of Thermal Switch “ALA” (M.I. XP31 Pin 4-9)
active.
Inverter
Fault
Overtemperature
Choke B Ph. V-B
36-135
Inverter filter overtemperature. Any of Thermal Switch “ALA” (M.I. XP31 Pin 4-9)
active.
Inverter
Fault
Overtemperature
Choke B Ph. W-C
36-136
Inverter filter overtemperature. Any of Thermal Switch “ALA” (M.I. XP31 Pin 4-9)
active.
Rectifier
Fault
E.P.O.
32-024
Depending on application: A02 stops rectifier.
Rectifier
Fault
Rectifier pre-
charge failure
32-025
DC bus under threshold P135.101.
Rectifier
Fault
Rectifier pre-
charge failure
32-026
DC bus under threshold P135.102.
Rectifier
Fault
Rectifier pre-
charge failure
32-027
KM1 feedback not OK.
Rectifier
Fault
Rectifier
Temperature fault
32-028
Rectifier Phase U temperature is greater then P 1152 setting (def = 95°C).
Rectifier
Fault
Rectifier
Temperature fault
32-029
Rectifier Phase V temperature is greater then P 1152 setting (def = 95°C).
Rectifier
Fault
Rectifier
Temperature fault
32-030
Rectifier Phase W temperature is greater then P 1152 setting (def = 95°C).
Rectifier
Fault
Rectifier DC
Overvoltage
32-031
DC overvoltage.
Rectifier
Fault
Rectifier de-
saturation failure
32-032
De-saturation Phase U (group A)
Rectifier
Fault
Rectifier de-
saturation failure
32-033
De-saturation Phase V (group A)
Rectifier
Fault
Rectifier de-
saturation failure
32-034
De-saturation Phase W (group A)
Table A.3 Fault Messages (continued)
Appendices
67
Summary of Contents for Liebert EXL S1
Page 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...
Page 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...
Page 52: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 48 This page intentionally left blank...
Page 74: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 70 This page intentionally left blank...
Page 130: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide...