Component
Type
Text Display
ID
Description
Bypass
Status
Bypass not prepared
01-004
Static switch board is not installed or the bypass voltage is over the threshold (P
106.i04).
Bypass
Status
Bypass fault
01-005
Set when a blocking fault is active in the stage.
Bypass
Status
Bypass warning
01-007
Set when at least one warning is active.
Bypass
Status
Bypass available with
delay
01-008
Set when the bypass and inverter are not synchronized.
Bypass
Status
Parallel bypass OK
01-029
All bypass inputs are OK.
Bypass
Status
Parallel bypass one
fault
01-030
One bypass input fault exists.
Bypass
Status
Parallel bypass at least
one OK
01-031
At least one bypass input is OK.
Bypass
Status
Parallel bypass fault
01-032
All bypass inputs are in fault.
Bypass
Status
Undelayed Bypass Ref.
Failure
01-040
Bypass reference failure notification without any delay.
Bypass
Status
Bypass is Centralized
01-041
The internal bypass is disabled; the UPS is using the centralized / common
(MSS) bypass.
Bypass
Status
Bypass Non-Blocking
Fault
01-042
Set when a non-blocking fault is active in the stage.
Bypass
Status
Bypass Global On
Request
01-078
Bypass Static Switch On command request on the shared bus
Bypass
Status
Bypass Global On
01-079
Bypass Static Switch on global status read from the shared bus.
Bypass
Status
Bypass Global Off
01-080
Bypass Static Switch Off Global status read from the shared bus.
Bypass
Status
Bypass mains is out of
tolerance
11-006
Bypass failure notification without any delay.
Bypass
Alarm
Bypass Input Switch
Open
21-012
Bypass input switch is open.
Charger/Booster
Status
Charger in Standby -
(not charging)
03-000
—
Charger/Booster
Status
Charger is on
03-001
—
Charger/Booster
Status
Charger is off
03-002
—
Charger/Booster
Status
Charger Forced On
03-003
—
Charger/Booster
Status
Charger Stopped due to
a Fault
03-038
—
Charger/Booster
Status
Charger in Current
Limitation
03-039
Displayed as long as the voltage reference is lower than the nominal.
Charger/Booster
Status
Charging Status OFF
03-040
—
Charger/Booster
Status
Charging Status INIT
03-041
—
Table A.1 Status Messages (continued)
Vertiv™ | Liebert® EXL S1 Operation and Maintenance Guide
50
Summary of Contents for Liebert EXL S1
Page 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...
Page 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...
Page 52: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 48 This page intentionally left blank...
Page 74: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 70 This page intentionally left blank...
Page 130: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide...