Component
Type
Text Display
ID
Description
Load
Alarm
Output Switch
Open
27-009
The output breaker MOB is open.
Load
Alarm
Load is currently
not supplied
27-010
Monolithic only: UPS is not supplying the load
Load
Alarm
Re-transfer is
inhibited
27-011
Load transfer to inverter inhibited due to overload (to be verified with overload
specification (see ).
MUN
Status
MUN has a warning
08-000
Set when at least one MUN stage is in warning.
MUN
Status
MUN has a fault
08-001
Set when at least one non-blocking fault is present on MUN.
MUN
Status
UPS Model
detection in
progress
08-003
MUN is searching for model information.
MUN
Status
MUN initialization
done
08-004
MUN is setup with auto detection.
MUN
Status
MUN reboot
required
08-005
MUN detects difference in environmental variables.
MUN
Status
System Started
08-011
Set at application standup; never reset.
MUN
Status
Acknowledge
Button Pressed
08-025
Acknowledge button has been pressed.
MUN
Status
UPS Time not valid
08-026
Set when date is < 1 Jan 2009.
MUN
Status
Life call in progress
08-033
Call in progress.
MUN
Status
Life call
rescheduled
08-034
Call rescheduled.
MUN
Status
Life modem not
detected
08-035
Set when MUN does not receive replies from modem.
MUN
Status
Parameter read
failed
08-054
Parameter can not be read from DSP.
Set when Parameter Reading returns with an exception.
Reset when Parameter Reading returns with OK.
MUN
Status
Parameter set
failed
08-055
Parameter cannot be written to DSP.
Set when Parameter Writing returns with an exception.
Reset when Parameter Writing returns with
OK
.
MUN
Status
Life Service Mode
08-060
Vertiv™ LIFE™ is in Service Mode, so emergency calls are not sent to station (used
when a service engineer is operating on the device).
MUN
Status
Ntp is
Disconnected from
Touchscreen
08-061
—
MUN
Status
Life interface Init in
Progress
08-079
Set at application startup; reset after one second.
MUN
Status
Life Events
Sampling started
08-095
Ignore events history and restart sampling from current time.
Table A.2 Alarm Messages (continued)
Vertiv™ | Liebert® EXL S1 Operation and Maintenance Guide
60
Summary of Contents for Liebert EXL S1
Page 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...
Page 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...
Page 52: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 48 This page intentionally left blank...
Page 74: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 70 This page intentionally left blank...
Page 130: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide...