1.3.1 Setpoints (User Adjustable)
The following will change the settings of the modules:
•
Screen Saver - Enable/Disable
•
Display Options
•
Customize Layout
•
Display Properties (Language, Theme, Back-Light Off Timer, Alarm Window Timeout, Auto-Logout
Timer, Display Brightness, Status Indicator Brightness, Calibrate Touchscreen)
•
Date & Time (Time Zone, Date, Local Time)
•
Format (Date. Time, Measurement System)
•
Custom Labels (Settings, Network Interfaces)
•
Audible Alarm - Silence, Enable, Disable
•
Automatic Battery Test - Enable/Disable, Test Duration (hh:mm:ss), Test Cycle (1-45 days), Test Inhibit Time
(1 - 1092 hr), Minimum Cell Voltage (1.65 - 2.9 V/cell)
•
Manual Battery Test - Start, Duration, Minimum Cell Voltage (1.65 - 2.9 V/cell)
•
Battery Equalize - Start, Charge Duration (1 - 72hr), Charge Voltage (2.3 - 2.9V/cell)
•
Manage Permissions - Operator and Admin PIN
•
Dial Control Setup - Center, Upper and Lower Meter
•
UPS Setting - Enable/Disable ECO Mode, Enable/Disable Audible Alarm, Enable/Disable Intelligent Parallel
Mode, Enable/Disable Dynamic Online Mode