RFS INSTALLATION INSTRUCTIONS
VERIZON HYBRIFLEX CABLE| Revision 1 | APRIL 2019
Visit
for the most current product specifications
Page 14 of 33
Fixation/Mounting of the Cable
The crush resistance may be lower for specific outer materials. For instance, this should be considered if
tightening the clamps (especially if these clamps have not been approved by RFS).
A number of different clamps may be used, we recommend using the SNAP-IN type. The SNAP-IN is suitable
for all fixing situations while at the same time it is the safest (most failure proof) clamp offering a large
number of exceptional advantages.
In any case the recommended and maximum clamp spacing shown in table 1 must always be considered. The
small spacing applies to severe site conditions (wind load, icing etc.); whereas the greater/recommended
spacing can be used for less exposed cable runs (e.g. indoor applications).
Table 1
HYBRIFLEX
Size
Spacing
HBF058 [5/8”]
0.7m (28”)
HBF078 [7/8”]
0.9m (3ft”)
HB114 [1-1/4”]
1.3m (4.25ft)
HB158 [1-5/8”]
1.5m (5ft)
HYBRIFLEX® tower accessories and installation tools
Note: Accessories can always be kitting with Hybrid assembly upon request. RFS recommended it accessories
be used to avoid any incompatibly issues that may arise during the installation process.
Caution!
Only use approved accessories and tools. Also note: RFS HYBRIFLEX
®
does not require the use of
grommets.
Note
: Hangers are sold in kits of 10 with hardware included (three options available)
Cable size
Model number
Short description
HB058
HB078
HB114
HB158
GKFROM60-58
GKFORM60-78
GKFORM60-114
GKFORM60-158
60 inch grounding kit
HB058
HB078
HB114
HB158
CLAMP-58 or SNAP-58 or SNAP-ST-
58
CLAMP-105 or SNAP-58 or SNAP-ST-
78
CLAMP-114 or SNAP-114 or SNAP-
ST-114
CLAMP-158 or SNAP-158 or SNAP-
Standard clamp bolt-
on hanger; Snap-in
hanger; Stackable
snap-in hanger