RFS INSTALLATION INSTRUCTIONS
VERIZON HYBRIFLEX CABLE| Revision 1 | APRIL 2019
Visit
for the most current product specifications
Page 32 of 33
Installation Instructions For Rack Mount and Tower Mount OVP’s
Caution!
Ensure that all DC power sources are disconnected or disabled prior to Wiring.
Installation tools required:
Tape, Wire Cutter, jacket stripping tool, termination lugs
Instructions for rack Mount
1.
Strip the outer jacket 5 ½ inches back
Fig. 1
2.
Twist the outer copper strands together
fig. 2
3.
Cut the non-insulated copper wire to 2 ½”
Fig. 3
4.
Strip the jacket off the insulated conductor 9/16 of an inch
Fig. 4
5.
Insert both wires into the Splitter connector
Fig. 5
6.
Install wires into rack mount unit using blade lugs,
Fig. 6.
7.
Repeat process for all 6 wires.
9/16 ”
”
Figure 4
5 ½”
2 ½”
”
Figure 1
Figure 2
Figure 3
Figure 4
Figure 6
Figure 5
9/16”