E50H2, E50H5 Installation Guide

#

Name

Description

R/W

Range

Additional information

BI9

Phase_Loss_A

Phase Loss Phase A

R

0=INACTIVE, 1=ACTIVE

Phase Loss - Phase A voltage dropped below the Phase Loss Threshold set by 

user

BI10

Phase_Loss_B

Phase Loss Phase B

R

0=INACTIVE, 1=ACTIVE

Phase Loss - Phase B voltage dropped below the Phase Loss Threshold set by 

user

BI11

Phase_Loss_C

Phase Loss Phase C

R

0=INACTIVE, 1=ACTIVE

Phase Loss - Phase C voltage dropped below the Phase Loss Threshold set by 

user

BI12

Power_Factor_A

Low Power Factor Phase A

R

0=INACTIVE, 1=ACTIVE

Phase A Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs 

to meter)

BI13

Power_Factor_B

Low Power Factor Phase B

R

0=INACTIVE, 1=ACTIVE

Phase B Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs 

to meter)

BI14

Power_Factor_C

Low Power Factor Phase C

R

0=INACTIVE, 1=ACTIVE

Phase C Power Factor less than 50% (commonly due to mis-wiring of CTs/PTs 

to meter)

BI15

RTC_Reset
(E50H5 only)

RTC Reset

R

0=INACTIVE, 1=ACTIVE

Real-Time Clock reset. This activates when the meter is powered after an 

interruption (since it does not use a battery backup). It indicates that the 

real-time clock has re-initialized to a default setting (00:00:00:00 on Jan 1, 

2000) and should not be relied upon. The clock runs, the meter operates and 

even logs data (E50H5A only), but the date and time are not correct until a 

Time_Synchronization occurs.

Data Logging (E50H5 only)

The E50H5 includes a data logging feature that records three meter parameters, accessible via BACnet using Trend_Log objects. All three Trend_Log objects utilize shared 
data logging resources in the meter, so all three are controlled in unison. All writable properties other than Log_Device_Property_Object are common to all three Trend_Log 
obects. Changes to these properties (Log_Enable, Start_Time, Stop_Time, Log_Interval, Stop_When_Full or Record Count) for any one of the objects will be reflected in 
the corresponding property of all three objects. The Log_Interval property is also common with the Demand_Subinterval (Present_Value of AV11), since logging records are 
updated synchronously with demand calculations.  

Default settings cause logging to begin immediately, with 15 minute intervals and no stop time. When full, the buffer will wrap and overwrite the oldest data first (unless the 
Stop_When_Full property is used).

Configuration:

Use Log_Device_Object_Property to select the meter parameter to log with each object. Set this property to point to Present_Value property of any of the Analog_Input 
objects. The default the values for the Log_Device_Object_Property of the three Trend_Log objects are set as follows:

•  TL1 = Real Energy Consumption (AI1 Present_Value)

•   TL2 = Reactive Energy Consumption (AI27 Present_Value)

•   TL3 = Total Real Power Present Demand (AI34 Present_Value)

The Log_Interval (& Demand Subinterval) can be set from 10 seconds to 32767 seconds (values of 1000 to 3276700). The subinterval timer, which determines how often the 
meter’s demand accumulators are updated, also triggers writing to the Trend_Log log buffers. Use the Log_Interval property to set the data logging time subinterval, in units 
of hundredths of a second (0.01 seconds). The default subinterval is 15 minutes (a value of 90000 in the Log_Interval property). The Buffer_Length is fixed at 5760, so at a 15 
minute interval setting, the buffers hold 60 days of data.

Use the Stop_When_Full property to select either Single Shot (Stop_When_Full = TRUE) or Continuous mode (Stop_When_Full = FALSE) for data logging. The default mode 
is Continuous. In Single Shot mode, the meter records data only until the buffer is full. Data for this time period is kept, but newer energy information is lost. In Continuous 
mode, the meter continues to record energy data as long as the meter is operating. The buffer can only hold 5760 entries at one time, however, so when the number of records 
exceeds 5760, the oldest entry is deleted to make room for the newest.

To start data logging with any of the three Trend_Log objects, set the Log_Enable property to TRUE or set the Start_Time and Stop_Time properties appropriately and wait 
for logging to commence at Start_Time.

BACnet Programming Information (cont.)

Summary of Contents for E50H Series

Page 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Page 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Page 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Page 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Page 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Page 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Page 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Page 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Page 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Page 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Page 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Page 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Page 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Page 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Page 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Page 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Page 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Page 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Page 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Page 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Page 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Page 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Page 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Page 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Page 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Page 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Page 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Page 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...