E50H2, E50H5 Installation Guide

By default, the Record_Count property of the Trend_Log objects is initialized to Zero. 

Reading Data:

Access logged data with corresponding timestamps via the Log_Buffer property of the Trend_Log object using the BACnet ReadRange service. The E50H5 supports both the 
“by Position” and “by Sequence Number” modes of the ReadRange service, but not the “by Time” mode.

Trend_Log Objects

Trend_Log Properties 

Used

R/W

Units

Additional information

Object_Name

R

Trend_Log_<n>

Where n is 1-3 (there are three instances of Trend_Log objects available)

Description

R

Trend_Log <n>

Where n is 1-3 (there are three instances of Trend_Log objects available)

Log_Enable

W

Binary

Set this to TRUE to enable logging or FALSE to disable logging.  The default is TRUE. 

The value is set to FALSE internally if logging stops for other reasons (i.e. buffer is full).

Start_Time

W

Date/Time

Sets the Date/Time when data logging will Start (if Log_enable is TRUE).  Set to a Date/Time earlier 

than the Local_Date/Local_Time properites of the Device object and Set Log_Enable TRUE to start 

logging immediately.

Stop_Time

W

Date/Time

Sets the Date/Time when data Logging will STOP (if still running). 

Stop_Time will be ignored if  ”wildcard” values are used in any of the fields.

Log_Device_Object_

Property

W

BACnetDeviceObjectProptertyReference

Set (point) this to the Present_Value of any of objects AI1 through AI49 

to establish which parameter to log. Default values are: 

    TL1 = Real Energy Consumption (Array of AI1 Present_Value) 

    TL2 = Reactive Energy Consumption (Array of AI27 Present_Value) 

    TL3 = Total Real Power Present Demand (Array of AI34 Present_Value)

Log_Interval

W

0.01 seconds

Logging period in hundredths of a second. 

Default is 90000 (15 minute intervals); minimum value is 1000 (10 seconds). This property can also 

be set to Zero, which changes all three Trend_Logs and the Demand calculation to a manual mode 

(sometimes referred to as “Sync to Comms”). In manual mode, the demand interval is updated and 

another record is logged upon a manual command, which is issued by writing the value 21211 to the 

Present_Value of object AV1.

Stop_When_Full

W

Binary

Set this to TRUE to stop logging when the buffer is full (single-shot mode) or FALSE to continue when 

full (wrap & overwtrite oldest data entries). 

Buffer_Size

R

5760

Length of Log Data buffer (# of records).  

Log_Buffer

R

List of BACnetLongRecord

Contains the data values logged, with timestamps

Record_Count

W

Unsigned 32-bit integer

This is an integer count of how many records logged since the Trend_Log objects were last reset.  

Writing a Zero to this property resets the logs of all three objects. This value defaults to Zero, but, by 

default, logging starts automatically at 15 minute intervals.

Total_Record_Count

R

Unsigned 32-bit integer

This is an integer count of how many records logged since the Trend_Log objects were created (the 

factory state of the meter). This count is unaffected by resetting the Record Count or by power 

failures. 

Event_State

R

Binary

BACnet Programming Information (cont.)

Summary of Contents for E50H Series

Page 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Page 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Page 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Page 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Page 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Page 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Page 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Page 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Page 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Page 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Page 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Page 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Page 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Page 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Page 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Page 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Page 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Page 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Page 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Page 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Page 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Page 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Page 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Page 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Page 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Page 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Page 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Page 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...

Reviews: