E50H2, E50H5 Installation Guide

Property

R/W

NV

Value Returned

Additional information

Object_List 

R

NV

DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI1

0,AI11,AI12,AI13,AI14,AI15,AI16,AI17,AI1

8,AI19,AI20,AI21,AI22,AI23,AI24,AI25,AI2

6,AI27,AI28,AI29,AI30,AI31,AI32,AI33,AI3

4,AI35,AI36,AI37,AI38,AI39,AI40,AI41,AI4

2,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI5

0,AI51,AI52,AV1,AV2,AV3,AV4,AV5,AV6,AV

7,AV8,AV9,AV10,AV11,BI1,BI2,BI3,BI4,BI5,

BI6,BI7,BI8,BI9,BI10,BI11,BI12,BI13,BI14,B

I15,TL1,TL2,TL3

BI15, TL1, TL2, and TL3 are present in the E50H5 only.

Device_Address_Binding

R

NV

{}

Database_Revsion

R

NV

0

Analog_Value Objects

Use the Present_Value property of the Analog_Value object for all writable variables in the meter other than those used specifically for BACnet configuration, Time 
Synchronization (in the Device Object), or Data Logging (in the Trend_Log objects).

Values are checked when written, and errors are returned for invalid entries. This table describes how the meter uses those variables, what values are valid, and what their 
defaults are. When writing values to the Present_Value properties of Analog_Value BACnet objects, there is a delay of up to about two seconds to validate and store the new 
value. An immediate read of the same property before that delay has elapsed can return the prior value (even if the new value was accepted). To read a value immediately after 
writing it, check the Reliability property first. When it reports a No_Fault_Detected status, the Present_Value of the object is current. 

These objects support the Description and Reliability object properties and all required Analog_Value object properties, but Present_Value is the only writable property.

#

Name

Description R/W

NV

Units

Range

Factory 

Default 

Value

Additional information

AV1

Config

Configuration R/W

n/a

n/a

Always 

returns 

”0” when 

read

Command Register:
- Write 30078 (0x757E) to clear all energy accumulators to 0 (All). 
- Write 21211 (0x52DB) to begin new Demand Sub-Interval calculation cycle and log 

another data value on Trend_Log objects TL1-TL3 (when the meter is in Manual “Sync-

to Comms” mode). This takes effect at the end of the next 1 second calculation cycle. 

Write no more frequently than every 10 seconds. Trend_Log values are only present on 

the E50H5 model.

- Write 21212 (0x52DC) to reset Max Demand values to Present Demand Values. Takes 

effect at the end of the next 1 second calculation cycle. Write no more frequently than 

every 10 seconds.

- Write 16498 (0x4072) to clear pulse counters to 0.

AV2

System_Type System Type

R/W

NV

n/a

40, 31, 12, 

11, 10

40

System_Type:
- Write 10 for Single-Phase: A + N
- Write 11 for Single-Phase: A + B
- Write 12 for Split-Phase: A + B + N
- Write 31 for 3-Phase  Δ: A + B + C, no N
- Write 40 for 3-Phase Y: A + B + C + N

AV3

CT_Ratio_

Primary

CT Ratio - 

Primary

R/W

NV

Amps

5-32000

100

Current Transducer Size - Primary Current Range (Default is set for 100 A CTs)

AV4

CT_Ratio_

Secondary

CT Ratio - 

Secondary

R/W

NV

1/Volts

1,3

1

Current Transducer Type – Secondary Interface 
- Enter 1 for CTs with 1V outputs (Default)
- Enter 3 for  CTs with 1/3V outputs

AV5

PT_Ratio

PT Ratio

R/W

NV

Value

0.01 -  320.0

1

Potential Transformer Ratio - The default is 1.00 (1:1), which is no PT attached. Set this 

value before setting the System Voltage (below).

BACnet Programming Information (cont.)

Summary of Contents for E50H Series

Page 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Page 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Page 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Page 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Page 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Page 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Page 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Page 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Page 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Page 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Page 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Page 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Page 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Page 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Page 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Page 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Page 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Page 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Page 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Page 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Page 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Page 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Page 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Page 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Page 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Page 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Page 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Page 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...