Vent-Axia Lo-Carbon Scala Plus HT Installation And Wiring Instructions Download Page 4

EN 

 
 

5.  Removing the grille, Firstly remove the front cover by carefully pulling each corner of the front panel until it is 

free to be removed from the inner grille (Fig 1). Unscrew the two screws at the bottom of the inner grille. The 
screws will remain in the inner grille but will be loose when the grille is ready to be removed (Fig 1).

 

Lift the 

inner grille from the bottom edge. 

6.  Remove the Spigot Ring from inside the carton and clip over the Spigot Adaptor making sure the lip on the 

Spigot Ring locates firmly inside the groove on the Spigot Adaptor (Fig 2).  Ensure that the Spigot Adaptor is 
firmly located onto the Base Housing and the shutter is still securely fastened and fully functional. 

7.  Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP.

 

8.  Using the Base Housing as a template, mark the fixing hole centres on the wall, carefully sliding the spigot 

into the Wall Liner. Secure the Base Housing into position using the screws and fixings provided ensuring the 
Skirt is located correctly into the Base Housing (Fig 3) 

9.  Ensure the Impeller rotates freely. 
10.  Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

12.  Replace the inner grille.

 

Replace the front panel.

 

 

13.  Switch the mains power supply on and check the fan is operating correctly.  

 
 

B.

 

SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST  BE ISOLATED FROM 

THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. 

 

 
 
 
 
 
 
1. SELECTING THE CONSTANT TRICKLE OPTION - 

Switch dip switch 2 into the ON position to activate the 

constant trickle operation. To disable the constant trickle option, move dip switch 2 into the OFF position (Fig. 6).

 

 

2. SELECTING THE TRICKLE SPEED (if enabled) 

This will determine the speed at which the fan will run continuously if the constant trickle speed option is enabled 
(1 above).  

 

Low trickle speed – Switch dip switch 1 into the OFF position (Fig. 6). 

 

High trickle speed – Switch dip switch 1 into the ON position (Fig. 6). 

 

3. SELECTING THE INSTALLATION RUNNING MODE  

This will determine the speed at which the fan will run when activated by either the Pull-cord/LS line/Humidity/PIR. 
 

 

Wall mode – Switch dip switch 3 into the OFF position (Fig. 6) 

 

Ducted mode – Switch dip switch 3 into the ON position (Fig. 6) 

 
4. SELECTING THE DELAY-ON OPTION

 

(HT model)

 - Switch dip switch 4 into the ON position to activate the 

delay-on feature. This will prevent the fan from going to boost for approximately 2 minutes. If the Switch Live is 
disconnected (switched off) within this period the fan will not boost. If the Switch Live is still active after the period 
the fan will boost. (Fig. 6). 

 
5. TIMER ADJUSTMENT ( HT model) 

The overrun time period is factory set to 15 minutes. The overrun time period may be adjusted from 5-30 
minutes by altering the adjuster on the control PCB [T] (Fig. 6). 

 

i. 

To REDUCE the operating time, turn the adjuster [T] ANTI-CLOCKWISE (Fig. 6). 

ii. 

To INCREASE the operating time, turn the adjuster [T] CLOCKWISE (Fig. 6). 

6. HUMIDITY ADJUSTMENT (HT model) 

The fan’s Humidity Set-Point is factory set to switch the fan on at 72%RH (Fig. 6). 

 

i. 

To LOWER the Set-Point, turn the Humidity Adjuster [H] ANTI-CLOCKWISE. This makes the fan more 
sensitive to RH%, i.e. the fan will come on at a lower RH% (Fig. 6). 

ii. 

To RAISE the Set-Point, turn the Humidity Adjuster [H] CLOCKWISE. This makes the fan less sensitive 
to RH%, i.e. the fan will come on at a higher RH% (Fig. 6). 

 
 
 
 

IMPORTANT 

On first power up, the fan will run through its initialization routine. 
On 

HT

 models the fan will switch on and off during this routine (Including the LED) 

Once complete after approximately 2 minutes, the fan will run as normal. 

Summary of Contents for Lo-Carbon Scala Plus HT

Page 1: ...de c blage FR Installations und Verdrahtungsanweisungen DE Montage en bekabelingsinstructies NL PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS VEUILLEZ LIRE...

Page 2: ...ith the rating label D The Fan should only be used in conjunction with the appropriate Vent Axia products E It is recommended that the connection to the fan connector terminals is made with flexible c...

Page 3: ...he grille is ready to be removed Fig 1 Lift the inner grille from the bottom edge 3 Remove the Spigot Ring from inside the carton and clip over the Spigot Adaptor making sure the lip on the Spigot Rin...

Page 4: ...led This will determine the speed at which the fan will run continuously if the constant trickle speed option is enabled 1 above Low trickle speed Switch dip switch 1 into the OFF position Fig 6 High...

Page 5: ...d cable clamps are securely fastened 4 Ensure the impeller rotates and is free from obstructions D SERVICING AND MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE P...

Page 6: ...ase soit conforme aux donn es de la plaque signal tique D Le ventilateur ne doit tre utilis qu avec les produits Vent Axia qui conviennent E Nous pr conisons le recours des c bles souples pour le racc...

Page 7: ...cessaires pour viter les solives et c bles cach s 2 Pour retirer la grille commencez pas retirer le capot avant en tirant doucement sur chaque coin de la fa ade jusqu ce qu il puisse tre retir de la g...

Page 8: ...sur le mur Calez le bo tier du ventilateur l emplacement voulu l aide des vis et fixations fournies en veillant ce que la jupe soit correctement centr e sur le bo tier du ventilateur Fig 3 9 V rifiez...

Page 9: ...Autrement dit le ventilateur se d clenche un taux HR plus lev Fig 6 C C BLAGE AVERTISSEMENT LE VENTILATEUR ET L QUIPEMENT DE COMMANDE AUXILIAIRE DOIVENT TRE ISOL S DE L ALIMENTATION SECTEUR PENDANT L...

Page 10: ...s entsprechenden Typenschilds bereinstimmt D Der L fter sollte nur in Verbindung mit den entsprechenden Produkten von Vent Axia eingesetzt werden E Es wird empfohlen eine Verbindung zu den Anschlusskl...

Page 11: ...den kann WICHTIG Achten Sie darauf Balken sowie versteckte Kabel zu vermeiden 2 Um das Gitter zu entfernen entfernen Sie zuerst die Frontabdeckung indem Sie vorsichtig an allen Ecken der Frontabdeckun...

Page 12: ...Sie die Befestigungsl cher an der Wand indem Sie den Geh useboden als Vorlage verwenden und der Luftstutzen vorsichtig in die Mauerh lse eingef hrt wird Befestigen Sie den Geh useboden mithilfe der be...

Page 13: ...Drehen Sie den Feuchteregler H im UHRZEIGERSINN um den Sollwert zu ERH HEN Dadurch reagiert der L fter weniger empfindlich auf Ver nderungen der Luftfeuchtigkeit d h der L fter schaltet sich bei h her...

Page 14: ...alleen samen met geschikte Vent Axia producten worden gebruikt E Gebruik van flexibele kabel voor het verbinden van de contactpunten van de ventilator F Wanneer de ventilator wordt gebruikt om lucht u...

Page 15: ...e onderkant van het binnenste rooster los De schroeven blijven in het binnenste rooster zitten maar zitten los wanneer het rooster moet worden verwijderd fig 1 Til het binnenste rooster aan de onderst...

Page 16: ...INSTELLING WAARSCHUWING DE VENTILATOR EN ONDERSTEUNENDE CONTROLEAPPARATUUR MOET GE SOLEERD WORDEN VAN DE STROOMVOORZIENING TIJDENS DE INSTALLATIE OF HET ONDERHOUD 1 SELECTEER DE OPTIE CONTINUSNELHEID...

Page 17: ...t kan nodig zijn de voedingskabel tussen de buitenkant van de basisbehuizing en de ommanteling door te leiden om te voorkomen dat deze bekneld raakt 3 Controleer of alle verbindingen juist zijn aanges...

Page 18: ...hole locations Emplacements des trous des vis de montage en surface Oberfl chenmontage Position der Schraubenl cher Opbouwmontage plaatsing schroefgaten Fig 4 Converting outlet spigot for side exit a...

Page 19: ...gler Modell HT Verstelinrichting luchtvochtigheid HT model H L N LS Top view of PCB cover showing pot locations and dip switch location Vue du dessus du cache de la carte lectronique illustrant l empl...

Page 20: ...ventilateur suit sa s quence d initialisation Sur les mod les HT le ventilateur s allume et s teint pendant cette s quence LED incluse Apr s cette s quence soit apr s environ deux minutes le ventilate...

Page 21: ...21 Fig 8 T HT wiring diagram Sch ma de c blage T HT T HT Schaltplan T HT aansluitschema...

Page 22: ...orrect electricity supply voltage is shown on the product rating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not autho...

Reviews: